Site icon Industrial Equipment MRO-Make purchasing faster and easier

Fluke 1555 FC 10 kV Insulation Tester Kit

FLUKE 1555

FLUKE 1555

Fluke 1555 FC 10 kV Insulation Tester Kit

Introduction:

The Fluke 1555 insulation resistance tester kit offers digital insulation testing up to 10 kV in an industrial strength case, with all the heavy duty leads and clips you need. Plus, the Fluke Connect wireless app performs tests and collects data while you stay a safe distance away.

Remote operation lets you spend as little time as possible in potentially hazardous zones. Real-time trending shows a live graph on your phone, rather than a hard-to-read set of changing values. And you can create reports quickly, simply using drag-and-drop – something you won’t find anywhere else.

Fluke insulation testers can now conduct the entire range of test voltages specified in IEEE 43-2000 with a best in class, 3 year warranty and CAT IV 600 V safety rating.

Other useful features:

Electrical Specifications
The tester\’s accuracy is specified for one year after calibration at operating temperatures of 0°C to 35°C. For operating temperatures outside the range (-20°C to 0°C and 35°C to 50°C), add ± .25% per °C, except on the 20% bands add ± 1% per °C.
Insulation Resistance Measurement
Test voltage (DC)
250 V Range < 250 kΩ,
250 kΩ to 5 GΩ
5 GΩ to 50 GΩ
> 50 GΩ
Accuracy (± reading) Unspecified
5%
20%
Unspecified
500 V Range < 500 kΩ
500 kΩ to 10 GΩ
10 GΩ to 100 GΩ
> 100 GΩ
Accuracy (± reading) Unspecified
5%
20%
Unspecified
1000 V Range < 1 MΩ
1 MΩ to 20 GΩ
20 GΩ to 200 GΩ
> 200 GΩ
Accuracy (± reading) Unspecified
5%
20%
Unspecified
2500 V Range < 2.5 MΩ
2.5 MΩ to 50 GΩ
50 GΩ to 500 GΩ
> 500 GΩ
Accuracy (± reading) Unspecified
5%
20%
Unspecified
5000 V Range < 5 MΩ
5 MΩ to 100 GΩ
100 GΩ to 1 TΩ
> 1 TΩ
Accuracy (± reading) Unspecified
5%
20%
Unspecified
10000 V Range < 10 MΩ
10 MΩ to 200 GΩ
200 GΩ to 2 TΩ
> 2 TΩ
Accuracy (± reading) Unspecified
5%
20%
Unspecified
Bar graph range 0 to 1 TΩ (1550C) – 0 to 2 TΩ (1555)
Insulation test voltage accuracy -0%, +10% at 1 mA load current
Induced AC mains current rejection 2 mA maximum
Charging rate for capacitive load 5 seconds per μF
Discharge rate for capacitive load 1.5 s/μF
Leakage current measurement Range 1 nA to 2 mA
Accuracy ± (5% + 2 nA)
Capacitance measurement Range 0.01 μF to 15.00 μF
Accuracy ± (15% rdg + 0.03 μF)
Timer Range 0 to 99 minutes
Resolution setting 1 minute
Resolution indication 1 second
Live circuit warning Warning range 30 V to 660 V AC/DC, 50/60 Hz
Voltage accuracy ± (15% + 2 V)
Software specifications FlukeView Forms™ basic software requires a PC running Windows XP, Windows Vista , Windows 7 or Windows 8.
General Specifications
Display 75 x 105 mm
Power 12 V lead-acid rechargeable battery, Yuasa NP2.8-12
Charger Input (AC) 85 V to 250 V AC 50/60 Hz 20 VA
This Class II (double insulated) instrument is supplied with a Class 1 (grounded) power cord. The protective earth terminal (ground pin) is not connected internally. The extra pin is for added plug retention only.
Dimensions 269 x 277 x 160 mm (10.6 x 10.9 x 6.3 in)
Weight 3.7 kg (8.2 lb)
Temperature (operating) -20°C to 50°C (-4°F to 122°F)
Temperature (storage) -20°C to 65°C (-4°F to 149°F)
Humidity 80% to 31°C decreasing linearly to 50% at 50°C
Altitude 2000 m
Enclosure sealing IP40
Input overload protection 1000 V AC
Electromagnetic compatibility EN 61326
Safety compliance IEC 61010-1: Overvoltage category II, Pollution Degree 2.
IEC 61010-2-030: Measurement 600V CAT IV / 1000V CAT III
IEC 61557-1, IEC 61557-2

Includes:

 

Exit mobile version