XIMADEN PAC16P Series Phase & Zero Cross Power Regulator
Introduction
PAC16P series integrates single-phase voltage regulation and power regulation. It has feature for slow start, slow shutdown, radiator overtemperature, current limit and overcurrent protection. It is suitable for resistive load and inductive load. It can be widely used for power adjustment in various fields of industry.
Ordering Code
Main Technical Data
Input | Load power supply and synchronous voltage | 50HZ, single phase 220VAC/ 380VAC, 60HZ need to be customized |
Automatic control signal | 4-20mA, Receiving impedance 120W | |
Fan power supply | 220VAC, 50HZ | |
Output | Adjust output resolution | Voltage regulation: 0.6 degrees; Power regulation: 20ms |
Drive output | ① Output: 12V pulse, variable pulse width, maximum driving current < 30mA. With P-type SSR, the voltage and power regulation mode is integrated ②pulse transformer output: slotted pulse, combined with MTX / MFC anti parallel module to realize single-phase voltage regulation and fully controlled rectification, but no power regulation mode. | |
Protection | Slow start and slow stop
No voltage contact input |
Close (ON): slow stop, fixed for 3 seconds; Open circuit (OFF): operation. (the slow start time is set by the internal potentiometer P3 for 0.2 ~ 120 seconds)
Not connected: running status. |
Emergency stop and automatic slow start | Overcurrent and overtemperature emergency stop during operation, and the action time of overcurrent and overtemperature protection shall not be greater than one power cycle(20ms) | |
Over temperature and over current protection
Normally open contact relay |
When the temperature of the radiator is higher than 80 ℃, it is prohibited to output and give an alarm. When the radiator is over-current, it is prohibited to output and give an alarm.
Remove: power on again after troubleshooting. Alarm relay: pure group 1A 250VAC |
|
Using Environment | Installation environment | Wall mounted vertical installation, good ventilation, no direct sunlight or thermal radiation, no corrosion and no flammability |
High humidity | High temperature, high humidity and altitude greater than 1000m shall be derated for using. Ambient relative humidity: ≤90% | |
Temperature | -10℃~+55℃ | |
The inductive load must use the external start stop switch and heater disconnection alarm HB function. |
Models
Model | Nominal current | Rated current | Sizes | Hole spacing | Cooling method |
PAC16P-B90-120-NON-11 | 120A | 60A | 220X92X170
(Profile heat dissipation) |
Ф4mm, 210mm | Natural cooling |
PAC16P-B90-150-NON-11 | 150A | 75A | Fan cooling | ||
PAC16P-B90-200-NON-11 | 200A | 100A | |||
PAC16P-B90-220-NON-11 | 220A | 110A | |||
PAC16P-B90-250-NON-11 | 250A | 125A | |||
PAC16P-B120-120-NON-11 | 120A | 60A | 242X110X210
(Fan cooling) |
Ф4mm, 160X100mm | Fan cooling |
PAC16P-B120-150-NON-11 | 150A | 75A | |||
PAC16P-B120-200-NON-11 | 200A | 100A | |||
PAC16P-B120-220-NON-11 | 220A | 110A | |||
PAC16P-B120-250-NON-11 | 250A | 125A | |||
PAC16P-B160-200-NON-11 | 200A | 105A | 244X160X195 | Ф9mm, 220X110mm | Fan cooling |
PAC16P-B160-220-NON-11 | 220A | 115A | |||
PAC16P-B160-250-NON-11 | 250A | 130A | |||
PAC16P-B160-300-NON-11 | 300A | 150A | |||
PAC16P-B160-340-NON-11 | 340A | 170A | |||
PAC16P-B227-220-NON-11 | 220A | 120A | 250X230X200 | Ф9mm, 230X140mm | Fan cooling |
PAC16P-B227-300-NON-11 | 300A | 155A | |||
PAC16P-B227-340-NON-11 | 340A | 175A | |||
PAC16P-B375-400-NON-11 | 400A | 200A | 375X128X235 | Ф6mm, 355X90mm | Fan cooling |
PAC16P-B375-500-NON-11 | 500A | 250A |
Dimensions