Single Phase EMI Filter DNF58-H-30A

$29.00

DNF58-H-30A Single Phase EMI Filter; AERODEV EMI FILTER DNF58-H-30A;

Single Phase EMI Filter DNF58-H-30A

Features

  • DNF58-H series is two stage filter with excellent insertion losses
  • Applicable to the Switching Power Supplies, UPS and other industrial automatic-control equipments
  • Customization accepted

Technical Parameters:

Type Rated

Voltage

Rated

Current

Hi-Pot Test Voltage Cx(μF)

 

±10%

Cy(nF)

 

±20%

L(mH)

 

-30%~+50%

R(MΩ)

 

±10%

Leakage Current

 

250V~50Hz

Line-Line Line-Ground
DNF58-G-20A 250V-50/60Hz 20A 1800VDC,2s 1800V-50/60Hz,2s 0.69 4.7 1.8 0.68 <1.1mA
DNF58-G-30A 250V-50/60Hz 30A 1800VDC,2s 1800V-50/60Hz,2s 1.0 3.3 1.5 1.0 <0.75mA
DNF58-G-40A 250V-50/60Hz 40A 1800VDC,2s 1800V-50/60Hz,2s 1.0 3.3 0.32 1.0 <0.75mA
DNF58-G-50A 250V-50/60Hz 50A 1800VDC,2s 1800V-50/60Hz,2s 1.0 3.3 0.32 1.0 <0.75mA
DNF58-H-20A 250V-50/60Hz 20A 1800VDC,2s 1800V-50/60Hz,2s 0.22 3.3 0.6 1.0 <0.75mA
DNF58-H-30A 250V-50/60Hz 30A 1800VDC,2s 1800V-50/60Hz,2s 0.22 3.3 0.4 1.0 <0.75mA
DNF58-H-40A 250V-50/60Hz 40A 1800VDC,2s 1800V-50/60Hz,2s 0.22 3.3 0.15 1.0 <0.75mA

Electrical Schematic:

DNF58 ELECTRICAL SCHEMATIC

Dimensions:

DNF58 DIMENSIONS

Installation Instructions:

1) Good electrical connection is needed between filter casing and equipment shell.

2) Connecting the filter’s input and output according to the provision on the label of LINE and LOAD.

3 )  The input wiring and the output wiring should be strictly separated, cannot be bundled together.

Brand

Suppliers