Three Phase EMI Filter DNF51-3PH-3x30A
Features:
- High performance
- Excellent characteristics of electromagnetic interference suppression
- Customization accepted
Technical Parameters:
Type | Rated
Voltage |
Rated
Current |
Hi-Pot Test Voltage | Cx(μF)
±10% |
Cy(nF)
±20% |
L(mH)
-30%~+50% |
R(MΩ)
±10% |
Leakage Current
250V~50Hz |
|
Line-Line | Line-Ground | ||||||||
DNF51-3PH-3x16A | 440V-50/60Hz | 16A | 1800VDC,2s | 2000V-50/60Hz,2s | 1.0 | 4.7 | 1.2 | 1.0 | <2.0mA |
DNF51-3PH-3x20A | 440V-50/60Hz | 20A | 1800VDC,2s | 2000V-50/60Hz,2s | 1.0 | 4.7 | 1.4 | 1.0 | <2.0mA |
DNF51-3PH-3x30A | 440V-50/60Hz | 30A | 1800VDC,2s | 2000V-50/60Hz,2s | 1.0 | 4.7 | 1.4 | 1.0 | <2.0mA |
DNF51-3PH-4x16A | 440V-50/60Hz | 16A | 1800VDC,2s | 2000V-50/60Hz,2s | 1.0 | 4.7 | 1.2 | 1.0 | <2.0mA |
DNF51-3PH-4x20A | 440V-50/60Hz | 20A | 1800VDC,2s | 2000V-50/60Hz,2s | 1.0 | 4.7 | 1.2 | 1.0 | <2.0mA |
DNF51-3PH-4x30A | 440V-50/60Hz | 30A | 1800VDC,2s | 2000V-50/60Hz,2s | 1.0 | 10.0 | 1.2 | 1.0 | <3.0mA |
Electrical Schematic:
Dimensions:
Installation Instructions:
1) Good electrical connection is needed between filter casing and equipment shell.
2) Connecting the filter’s input and output according to the provision on the label of LINE and LOAD.
3 ) The input wiring and the output wiring should be strictly separated, cannot be bundled together.