Fluke 1577 Insulation Multimeter

$784.00

Fluke 1577 Insulation Multimeters combine a digital insulation tester with a full-featured, true RMS digital multimeter in a single, compact, handheld unit, which provides maximum versatility for both troubleshooting and preventative maintenance.

Fluke 1577 Insulation Multimeter

Introduction:

The Fluke 1587 and 1577 Insulation Multimeters combine a digital insulation tester with a full-featured, true RMS digital multimeter in a single, compact, handheld unit, which provides maximum versatility for both troubleshooting and preventative maintenance.

Whether you work on motors, generators, cables, or switch gear, the Fluke 1587/1577 Insulation Multimeters are ideally suited to help you with your tasks and at a cost that is far less than buying the two products.

Specifications
Voltage DC Maximum voltage 1000 V
Accuracy ±(0.2%+2)
Maximum resolution 0.001 V
Voltage AC Maximum voltage 1000 V
Accuracy ±(2%+3)
Maximum resolution 0.1 mV
Current DC Maximum amps 400 mA
Amps accuracy ±(1.0%+2)
Maximum resolution 0.001 mA
Current AC Maximum amps 400 mA
Amps accuracy ±(2.0%+2)*
Maximum resolution 0.01 mA
Resistance Maximum resistance 50 MΩ
Accuracy ±(1.2%+2)
maximum resolution 0.1Ω
Insulation Test
Minimum test current @ 1kΩ/V 1 mA
Test voltages 500, 1000 V
Maximum resistance per test voltage 50 V
100 V
250 V
500 V
1000 V 600 MΩ
Maximum resolution per test voltage 50 V 0.01 MΩ
100 V 0.01 MΩ
250 V 0.1 MΩ
500 V 0.1 MΩ
1000 V 0.1 MΩ
Accuracy per test voltage 50 V ±(3% + 5)
100 V ±(3% + 5)
250 V ±(1.5% + 5)
500 V ±(2.0% + 5)
1000 V ±(2.0% + 5)
Environmental Specifications
Operating temperature –20°C to +55°C
Storage temperature -40°C to +60°C
Humidity (without condensation) 0% – 95% (10°C – 30°C)
0% – 75% (30°C – 40°C)
0% – 40% (40°C – 55°C)
Operating altitude 2000 m
Safety Specifications
Overvoltage category Complies with ANSI/ISA 82.02.01 (61010-1) 2004, CAN/CSA-C22.2 NO. 61010-1-04, and IEC/EN 61010-1 2nd Edition for measurement CAT III 1000 V and CAT IV 600 V
Agency approvals 2000 m CAT III 1000 V, CAT IV 600 V; 3000 m CAT II 1000 V, CAT III 600 V
Mechanical and General Specifications
Size 203 x 100 x 50 mm (with holster)
Weight 624 g
Warranty 3 years
Battery life alkaline Meter use 1000 hours
Insulation test use Meter can perform at least 1000 insulation tests with fresh alkaline batteries at room temperature. These are standard tests of 1000 V into 1 MΩ with a duty cycle of 5 seconds on and 25 seconds off.
IP rating IP40

Includes:

  • Remote probe
  • Test leads
  • Alligator clips
  • Hard case
  • Four AA alkaline batteries
  • Quick reference guide
  • CD rom with manual
Weight 0.8 kg
Dimensions 203 × 100 × 50 mm
Brand