Fluke 316 Clamp Meter

Fluke 316 Clamp Meter

Fluke 316 Clamp Meter

Introduction:

The Fluke 312, 316 and 318 clamp meters measures ac and dc voltage, ac current, resistance, and continuity.

Electrical Specifications:

The accuracy specification is defined as ±(% reading + digits) at 23 ℃± 5℃。

Function Range Resolution Accuracy (% reading + digits)
312 316&318
AC Amps2

( 50~500Hz)

40.00A

400.0A

1000A

0.01A

0.1A

1A

1.9%±5 (50~60Hz) 1.9%±5 (50~60Hz)

2.5%±5 (60~500Hz)

DC Amps 40.00A

400.0A

1000A

0.01A

0.1A

1A

2.5%±5
AC Volts2 ( 50~500Hz) 400.0V

750V

0.1V

1V

1.2%±5 1.5%±5
DC Volts 400.0V

1000V

0.1V

1V

0.75%±2 1%±2
Resistance(ohm) 400.0W

4000W

0.1W

1W

1%±3 1%±3
Continuity On at <50W
Diode Test Up to 2 V
Min Max 500 ms acquisition time
Input Impedance 10MW
Auto Shut-off After 30 min ±2 min. Disabled in Min Max. Can be disabled as a power up option ( hold down the peak button)
Auto range Available in the following measurement funtions: Volts & Ohms (Amps for 312 only)
Overload Protection 600 Vrms per EN61010 CAT III 600V
Weight 0.37 kg
Dimensions 254 × 66 × 37 mm
Brand

Suppliers