Fluke 902 HVAC True RMS Clamp Meter

Fluke 902 HVAC Clamp Meter

Fluke 902 HVAC True-RMS Clamp Meter

Introduction:

The Fluke 902 is a hand-held battery-operated HVAC Clamp Meter (“the Meter”) that measures:

  • AC current
  • DC current (up to 200 µA for flame rod testing)
  • AC and DC voltages
  • Capacitance
  • Resistance
  • Continuity
  • Temperature in both Celsius (°C) and Fahrenheit (°F)

The Meter comes with:

  • Two AA alkaline batteries (installed)
  • Users Manual
  • Soft carrying case
  • TL75 Test Leads (one pair)
  • 80BK Integrated DMM Temperature Probe
Function Range Resolution Accuracy
Voltage DC 0 – 600 V 0.1 V 1 % ± 5 counts
Voltage AC

(True Rms)

0 – 600 V 0.1 V 1 % ± 5 counts

(50/60 Hz)

Current AC

(True Rms)

0 – 600 A 0.1 A 2.0 % ± 5 counts

(50/60 Hz)

Current DC 0 – 200 µA 0.1 µA 1.0 % ± 5 counts
Resistance 0 – 999 Ω

0 – 9999 Ω

0.1 Ω

1.0 Ω

1.5 % ± 5 counts
Continuity < 30 Ω    
Temperature -10 to 400 °C 0.1 °C 1 % ± 0.8 °C
Capacitance 1-100 µF

100-1000 µF

0.1 µF

1 µF

1.9 % ± 2 counts

General Specifications:

Operating Temperature -10 C to +50 C
Storage Temperature -40 C to +60 C
Operating Humidity Non condensing (< 10 C)

90 % RH (10 C to 30 C)

75 % RH (30 C to 40 C)

45 % RH (40 C to 50 C)

(Without Condensation)

Operating Altitude 2500 meters above mean sea level
Storage Altitude 12,000 meters above mean sea level
IP Rating IP 30 per IEC 60529
Vibration Requirements MIL-PRF-28800F Class 2 random vibration
EMI, RFI, EMC EMI: instrument unspecified for use in EMC field • 0.5 V / Meter

EMC: Meets all applicable requirements in EN61326-1

Temperature Coefficients 0.1   x (specified accuracy)/ C  (<18 C or >28 C)
   
Size (H X W X L) 240 x 80 x 40 mm
Weight 310 g
Design Standards and Compliance IEC 61010, IEC 61010-2-032,CE
Over-voltage Category 600 V, CAT III per IEC 1010-1
Power Requirements Two AA Batteries, NEDA 15 A, IEC LR6
   

 

Weight 0.31 kg
Dimensions 240 × 80 × 40 mm
Brand